Earthing (called grounding in some countries) is a critical safety system that provides a low-resistance path for fault currents to flow safely to ground. In a solar installation, proper earthing protects against electric shock, fire, and equipment damage by ensuring that any fault condition – such as damaged insulation or a lightning strike – results in current flowing harmlessly to earth rather than through people or causing fires.
A properly earthed solar system connects all exposed metal parts (panel frames, mounting rails, inverter casings) to the main earthing terminal of the property, which connects to the ground via an earth electrode. This creates an equipotential zone where touching any metal part during a fault won’t result in dangerous voltage differences. UK regulations require all solar installations to be properly earthed in accordance with BS 7671 (the IET Wiring Regulations).
This guide explains why earthing matters, what the UK regulations require, how solar systems are earthed in practice, common configurations including the PME considerations that catch many homeowners by surprise, and what to check to ensure your system is properly protected.
Earthing at a Glance
| Purpose | Safety – protect people and equipment from faults |
| UK regulations | BS 7671 (IET Wiring Regulations) |
| What’s earthed | All exposed metalwork; some DC circuits |
| Connection point | Main earthing terminal (MET) |
| Installer responsibility | Must certify earthing is correct |
| Homeowner check | Green/yellow earth wires visible at inverter |
Why Earthing Matters
Protection Against Electric Shock
| Scenario | Without Earthing | With Earthing |
|---|---|---|
| Insulation fault | Metal becomes live | Fault current trips protection |
| Touching metal | Shock through body to ground | Current flows through earth path |
| Voltage on frame | Can remain indefinitely | Cleared in milliseconds |
For the broader context on solar electrical safety – DC voltages, what’s safe to touch, and emergency response – see our guide on can solar panels electrocute you.
Fire Prevention
| Risk | How Earthing Helps |
|---|---|
| Fault current | Flows safely to earth; trips protection |
| Arcing | Low-impedance path prevents sustained arcs |
| Overheating | Fault cleared before heat builds up |
| Lightning | Energy dissipated to ground |
Sustained DC arcs are one of the few realistic fire-ignition pathways on a solar installation. Modern inverters increasingly include arc-fault detection circuitry as a backup to good earthing – see our arc fault detection guide for the detail.
Equipment Protection
| Threat | Protection Mechanism |
|---|---|
| Voltage surges | SPDs divert to earth |
| Lightning strikes | Current path to ground |
| Static buildup | Dissipated through earth |
| EMI/interference | Reference point for electronics |
UK Regulatory Framework
Key Standards
| Standard | Coverage |
|---|---|
| BS 7671 | IET Wiring Regulations – main electrical standard |
| Section 712 | Specific requirements for solar PV systems |
| BS EN 62305 | Lightning protection systems |
| MCS standards | Installation requirements for certification |
BS 7671 is published jointly by the Institution of Engineering and Technology and the British Standards Institution, and although it is technically non-statutory it is referenced in numerous UK regulations and treated as the authoritative method of compliant electrical installation. The IET’s BS 7671 earthing and bonding FAQs are the most accessible reference for the topic.
BS 7671 Requirements
| Requirement | Details |
|---|---|
| Protective earthing | All exposed conductive parts connected to earth |
| Equipotential bonding | Metal parts at same potential |
| Earth fault loop impedance | Low enough to trip protection quickly |
| Documentation | Test results recorded on certificate |
Section 712 (Solar PV)
| Topic | Requirement |
|---|---|
| DC side earthing | Depends on system configuration |
| AC side earthing | Standard installation requirements |
| Surge protection | Risk assessment required |
| Labelling | Warning labels for DC presence |
Section 712 sits within a broader regulatory stack covered by Part P of the Building Regulations – which makes solar PV electrical work notifiable and forces it through a competent-person scheme. Our Part P guide covers the certification side in detail.
Who’s Responsible
| Party | Responsibility |
|---|---|
| Installer | Design and install correct earthing |
| Installer | Test and certify earthing |
| DNO | Provides earth (in most systems) |
| Homeowner | Ensure competent installer used |
Types of Earthing Systems
UK Earthing Arrangements
| Type | Description | Common In |
|---|---|---|
| TN-S | Separate neutral and earth from substation | Older properties |
| TN-C-S (PME) | Combined neutral-earth; separated at property | Most modern properties |
| TT | Local earth electrode at property | Rural areas; overhead supplies |
TN-S System
| Aspect | Details |
|---|---|
| Earth source | Cable sheath from substation |
| Reliability | Very good |
| Impedance | Low |
| Solar compatibility | Straightforward |
TN-C-S (PME) System
| Aspect | Details |
|---|---|
| Earth source | DNO’s combined neutral-earth (PEN) |
| At property | Neutral and earth separated |
| Special consideration | Open PEN risk |
| Solar consideration | May need additional earth electrode |
TT System
| Aspect | Details |
|---|---|
| Earth source | Local earth electrode (rod) |
| Where used | No DNO earth available |
| Impedance | Higher; depends on soil |
| Protection | RCD essential |
| Solar consideration | Earth electrode resistance critical |
Components of Solar System Earthing
What Gets Earthed
| Component | Earthing Requirement |
|---|---|
| Panel frames | Connected to earth via mounting |
| Mounting rails | Bonded together and to earth |
| Inverter casing | Earth terminal connection |
| AC isolator | Metal enclosure earthed |
| DC isolator | Metal enclosure earthed |
| Cable trays/conduit | Metal parts earthed |
For a refresher on what each of these components does in the wider system – see our breakdown of solar panel system components.
Panel Frame Earthing
| Method | Details |
|---|---|
| Through mounting clamps | Clamps provide electrical continuity |
| Dedicated earth bonding | Separate earth wire to frame |
| Grounding clips | Pierce anodising for good contact |
| Verification | Continuity testing required |
Mounting System Earthing
| Component | Earthing Method |
|---|---|
| Rails | Bonded together; connected to earth |
| Roof hooks/brackets | Continuity through fixings |
| Earth wire | Typically 6mm² minimum |
| Connection point | Main earthing terminal |
Inverter Earthing
| Connection | Details |
|---|---|
| Earth terminal | Dedicated connection point inside |
| AC earth | Through supply cable CPC |
| Additional bonding | May be required to mounting |
| Internal components | Manufacturer’s responsibility |
DC Side Earthing
Functional vs Protective Earthing
| Type | Purpose |
|---|---|
| Protective earthing | Safety – fault current path |
| Functional earthing | System operation requirement |
| Frames/metalwork | Always protective earthed |
| DC conductors | Depends on inverter type |
Grounded vs Ungrounded DC Systems
| Type | DC Negative | Common With |
|---|---|---|
| Grounded (earthed) | Connected to earth | Some older/US inverters |
| Ungrounded (floating) | Not connected to earth | Most European inverters |
| UK standard | Ungrounded typical | Transformerless inverters |
Transformerless Inverters
| Aspect | Details |
|---|---|
| DC system | Floating (ungrounded) |
| Galvanic isolation | None between DC and AC |
| Fault detection | Insulation monitoring required |
| Frame earthing | Still required for safety |
Microinverter and module-level systems push the DC/AC boundary up to the panel itself, eliminating the high-voltage DC string entirely. From an earthing perspective this simplifies the picture – see our guide to microinverters for residential solar for the full trade-offs.
Insulation Monitoring
| Function | Details |
|---|---|
| What it monitors | Insulation resistance DC side |
| Detection | Earth fault on DC conductors |
| Action | Shuts down inverter if fault detected |
| Built into | All transformerless inverters |
AC Side Earthing
Standard Requirements
| Component | Requirement |
|---|---|
| CPC (earth wire) | In AC cable from inverter |
| Connection | To consumer unit earth bar |
| Size | Related to live conductor size |
| Continuity | Tested during commissioning |
Consumer Unit Connection
| Item | Details |
|---|---|
| Dedicated circuit | Solar on own breaker/RCBO |
| Earth connection | To main earth bar |
| RCD protection | Type A or Type B depending on inverter |
| Documentation | Recorded on electrical certificate |
RCD Type Requirements
| Inverter Type | RCD Required | Reason |
|---|---|---|
| With transformer | Type A | Standard AC faults only |
| Transformerless | Type A + built-in DC detection | Most inverters have this |
| Some transformerless | Type B | If no internal DC fault detection |
Surge Protection and Earthing
Why SPDs Need Good Earthing
| Factor | Explanation |
|---|---|
| SPD function | Diverts surge current to earth |
| Low impedance needed | Surge must flow easily to earth |
| Poor earth | SPD can’t protect effectively |
| Good earth | Surge energy safely dissipated |
SPD Earthing Requirements
| Location | Earth Connection |
|---|---|
| DC SPD (at array) | Short connection to mounting earth |
| DC SPD (at inverter) | To main earth terminal |
| AC SPD | To consumer unit earth bar |
| Lead length | As short as possible |
Lightning Protection
| Aspect | Details |
|---|---|
| Direct strikes | Rare; separate LPS if needed |
| Induced surges | More common; SPDs protect |
| Risk assessment | Required by BS 7671 |
| Rural/exposed sites | Higher risk; SPDs recommended |
For severe-weather risks more broadly – including how to react after a lightning strike or major storm event – see our storm damage and solar panels guide.
Equipotential Bonding
What It Means
| Concept | Explanation |
|---|---|
| Equipotential | All metal at same voltage |
| Bonding | Connecting metal parts together |
| Purpose | No voltage difference = no shock |
| Zone | All bonded parts form protected zone |
Main Bonding
| What’s Bonded | Requirement |
|---|---|
| Gas pipes | Within 600mm of meter |
| Water pipes | Within 600mm of entry |
| Oil pipes | If applicable |
| Structural steel | If accessible |
Supplementary Bonding
| Where | Details |
|---|---|
| Bathrooms | All metal within zones bonded |
| Solar installation | Metal parts on roof bonded |
| Purpose | Local equipotential zone |
Solar-Specific Bonding
| Component | Bonding Requirement |
|---|---|
| All panel frames | Bonded to each other |
| All mounting rails | Continuous bond across array |
| Connection to MET | Single earth conductor |
| Minimum conductor | Typically 6mm² or 10mm² |
Testing and Verification
Tests Required
| Test | What It Checks |
|---|---|
| Earth continuity | All earth connections complete |
| Earth fault loop impedance (Zs) | Fault current can flow; protection will trip |
| Insulation resistance | No breakdown between live and earth |
| RCD operation | Trips at correct current/time |
Continuity Testing
| What’s Tested | Acceptable Result |
|---|---|
| CPC continuity | Low resistance (<1Ω typically) |
| Bonding conductors | Low resistance |
| Frame bonding | Continuity through all frames |
| Rail bonding | Continuity across mounting |
Earth Fault Loop Impedance
| System Type | Typical Zs |
|---|---|
| TN-S | Low (good) |
| TN-C-S (PME) | Low (good) |
| TT | Higher (RCD essential) |
| Requirement | Low enough for protection to operate |
Documentation
| Document | Contains |
|---|---|
| Electrical Installation Certificate | All test results; earth values |
| Schedule of Test Results | Detailed measurements |
| MCS certificate | Confirms compliant installation |
Common Earthing Issues
Installation Problems
| Problem | Consequence |
|---|---|
| Missing earth connection | No protection; shock risk |
| Poor contact to frame | High impedance; protection may not trip |
| Undersized conductor | May not carry fault current |
| Corroded connection | High resistance; ineffective |
Anodised Frame Issues
| Issue | Solution |
|---|---|
| Anodising is insulating | Must pierce coating for earth |
| Standard clamps | May not make good contact |
| Grounding clips | Designed to pierce anodising |
| Star washers | Can help improve contact |
Degradation Over Time
| Factor | Effect |
|---|---|
| Corrosion | Increased resistance |
| Loose connections | High impedance; heating |
| Dissimilar metals | Galvanic corrosion |
| UV degradation | Wire insulation damage |
PME (TN-C-S) Considerations
| Issue | Details |
|---|---|
| Open PEN conductor | Rare but serious fault |
| Risk | Voltage on earthed metalwork |
| Solar consideration | Roof metalwork becomes hazard |
| Mitigation | Additional earth electrode may be required |
Earth Electrodes
When Required
| Situation | Electrode Needed? |
|---|---|
| TT system | Yes – main earth source |
| PME with solar | Sometimes – risk mitigation |
| Lightning protection | Yes – for LPS |
| Standard TN system | Not usually for solar |
Types of Earth Electrode
| Type | Details |
|---|---|
| Earth rod | Copper-clad steel; driven into ground |
| Earth plate | Buried copper plate |
| Earth tape | Buried copper tape |
| Foundation earth | Concrete-encased electrode |
Earth Electrode Resistance
| System | Maximum Resistance |
|---|---|
| TT with 30mA RCD | <1667Ω (but lower better) |
| TT practical target | <200Ω preferred |
| Lightning protection | <10Ω typically |
| Factors affecting | Soil type; moisture; depth |
Installer Responsibilities
Design Requirements
| Task | Details |
|---|---|
| Assess existing earthing | TN-S, TN-C-S, or TT? |
| Design earth system | Conductor sizes; routes |
| Risk assessment | Lightning; surge protection |
| PME considerations | Additional measures if needed |
Installation Requirements
| Task | Standard |
|---|---|
| All metalwork earthed | BS 7671 |
| Correct conductor sizes | BS 7671 tables |
| Good connections | Low resistance; secure |
| Protected routes | UV resistant; mechanical protection |
Testing and Certification
| Requirement | Details |
|---|---|
| All tests completed | Before energising |
| Results recorded | On schedule of results |
| Certificate issued | Electrical Installation Certificate |
| Competent person | Part P registered or equivalent |
What Homeowners Should Know
Signs of Proper Earthing
| Visual Check | What to Look For |
|---|---|
| Earth wires | Green/yellow wires visible at inverter |
| Connections | Secure; not corroded |
| Documentation | Test results on certificate |
| Earth values recorded | Zs, Ze, or Ra on certificate |
Warning Signs
| Concern | Action |
|---|---|
| Tingling from metal parts | Contact electrician immediately |
| No earth wire visible | Query with installer |
| Tripping RCDs | May indicate earth fault |
| Missing certificates | Request from installer |
If you see signs of an earthing fault – particularly an inverter throwing repeated insulation-resistance errors – our solar panel fault-finding guide walks through the safe diagnostic sequence before you call out an electrician.
Maintenance Considerations
| Check | Frequency |
|---|---|
| Visual inspection | Annual |
| Look for corrosion | Annual |
| Loose connections | Annual |
| Full electrical test | Every 5-10 years |
Frequently Asked Questions
Basic Questions
| Question | Answer |
|---|---|
| Is earthing really necessary? | Yes – safety critical; legally required |
| Who is responsible? | Installer must design, install, and certify |
| Can I check it myself? | Visual only; testing needs electrician |
| What if it’s wrong? | Contact installer; serious safety issue |
Technical Questions
| Question | Answer |
|---|---|
| Do panels need individual earths? | Bonded together; one connection to MET |
| What’s the green/yellow wire? | Earth (CPC – circuit protective conductor) |
| Why does my inverter mention earthing? | Some need specific configuration |
| Is DC earthed? | Usually floating; frames earthed |
Summary
| Aspect | Key Point |
|---|---|
| Purpose | Safety – shock and fire protection |
| UK standard | BS 7671 (IET Wiring Regulations) |
| What’s earthed | All exposed metalwork (frames, rails, inverter) |
| DC system | Usually floating; frames earthed |
| AC system | Standard earthing through CPC |
| Testing | Continuity, loop impedance, RCD |
| Documentation | Results on Electrical Installation Certificate |
| Homeowner role | Use competent installer; keep certificates |
Earthing is a fundamental safety system that protects you from electric shock and your home from fire. Every solar installation must be properly earthed in accordance with BS 7671, with all exposed metal parts – panel frames, mounting rails, inverter casing – connected to the main earthing terminal of your property. This creates an equipotential zone where fault currents flow safely to earth rather than through people.
Your installer is responsible for designing, installing, and testing the earthing system. This includes ensuring all metal parts are bonded together, conductors are correctly sized, and connections are secure. All test results should be recorded on your Electrical Installation Certificate, including earth fault loop impedance values that prove the system will operate safely.
Most UK solar installations use transformerless inverters with floating (ungrounded) DC systems. The DC conductors themselves aren’t connected to earth, but all metalwork is. The inverter monitors insulation resistance on the DC side and will shut down if it detects a fault. This approach provides safety while maximising efficiency.
As a homeowner, you can visually check that green/yellow earth wires are visible and connections appear secure, but proper testing requires a qualified electrician. Any concerns – particularly tingling sensations from metal parts – should be investigated immediately. Keep your certificates safe; they document that your system was properly installed and tested.
The PME question is the one most homeowners should ask their installer. If your home has a TN-C-S (PME) supply – which most modern UK homes do – the rare but serious “open PEN” fault scenario can put voltage on the earthed metalwork of an outdoor installation. Solar panels on a roof are exactly that. Whether your installer plans to fit an additional earth electrode, use a “PME-friendly” inverter with class II isolation, or rely on the DNO supply earth alone is a real design decision, and you should expect a clear answer.
The other thing worth checking on day one: your Electrical Installation Certificate should arrive in your inbox or by post within a few weeks of commissioning, with measured values for earth continuity, earth fault loop impedance, and insulation resistance. If it doesn’t, chase your installer – that document is the legal proof your system was properly tested.